Specification Details For ANTSPACE HK3 | ||
Version | ANTSPACE HK3 | |
Dimensions (L*W*H) (mm) | 6058*2438*2896 | |
Miner Capacity | 210 units -S19 Hyd. Series miner | |
Container Certification | China Classification Society Certification | |
Safety Certification | North America/Standards:NFPA 79:2021,UL 508A:2018 R8.21, CSA C22.2 No. 14-18,ANSI/ISO 12100:2012 EU/Standards:EN ISO 12100,EN 60204-1 |
|
Operating Power(kW) | 1047~1050 | |
PUE(Power Usage Effectiveness) | 1.022(Excluding cooling tower)/1.036(Including cooling tower) | |
Input Voltage and Frequency | 415V±5% 60Hz(North America) 400V±5% 50Hz(EU、Middle East) |
|
Detailed Characteristics | ||
Shipping Weight(T) | 8 | |
Operating Weight (T) | 12 | |
Main Switch of Power Distribution Cabinets(A) | 1200(North America) 1250(EU、Middle East) |
|
Rated Current(A) | 952 | |
Standard Power(kW) | 1049 | |
Maximum Power(kW) | 1050 | |
Rated Current per Miner(A) | 10 | |
Inlet Cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase: L1 single core cable 600kcMil(300mm²)x4 L2 single core cable 600kcMil(300mm²)x4 L3 single core cable 600kcMil(300mm²)x4 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2 |
|
Connection Interface(Cooling Tower) | DN125(GB/T 9119-2010 PN16 DN125) | |
Connection Interface(Plate Heat Exchage Interface) | DN100(GB/T 9119-2010 PN16 DN100) | |
Flow Rate(m³/h) | >85 | |
Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 | |
Specification Details For Dry-Wet Towers | ||
One of the following two Dry-Wet Towers can be chosen based on the personalized demand. | ||
Product Overview | ||
Type | Dry-Wet Tower Traditional Type (DWT-T) | Dry-Wet Tower Container Type (DWT-C) |
Dimensions(L*W*H)(mm) | 5800*2240*4200 | 6058*2438*2896 |
Heat Dissipation Capacity(kW) | 1000 | 1000 |
Outlet Temperature @ 28℃ Wet Bulb Temperature | 35℃ | 35℃ |
Container Certification | None | China Classification Society Certification |
Safety Certification | North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, | North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, |
CSA C22.2 No. 14-18, ANSI/ISO 12100:2012 | CSA C22.2 No. 14-18, ANSI/ISO 12100:2012 | |
EU Standards: EN ISO 12100, EN 60204-1 | EU Standards: EN ISO 12100, EN 60204-1 | |
Operating Power(kW) | 14~28 | 14~28 |
Motor Rated Voltage and Frequency | 415V±5% 60Hz(North America) | 415V±5% 60Hz(North America) |
400V±5% 50Hz(EU、Middle East) | 400V±5% 50Hz(EU、Middle East) | |
Detailed Characteristics | ||
Shipping Weight(T) | 5 | 6 |
Operating Weight(T) | 9 | 10 |
Connection Interface(Container) | DN125(GB/T 9119-2010 PN16 DN125) | DN125(GB/T 9119-2010 PN16 DN125) |
Water Resupply Pipe Interface | DN40(Internal thread) | DN40(Internal thread) |
Drain Pipe Interface | DN65(Internal thread) | DN65(Internal thread) |
Noise Level @25℃, 16m | 70dBA | 70dBA |
Water Consumption(m³/h) | 1~1.5 | 1~1.5 |